Woodward ProTech TPS Safety System

Functions Safety PLC with integrated overspeed protection for steam, gas, or hydro turbines
Accepts up to 30 configurable discrete/analog inputs and 3 speed inputs
Triple modular redundant (TMR) architecture with 2-out-of-3 voting logic
Custom programmable safety functions
Supports online repair and module replacement
Name Woodward ProTech TPS Safety System
Auxiliary Voltage LV: 18–32 V DC
HV: 88–264 V AC / 90–150 V DC
Actuator Output N/A
Digital Inputs Up to 30 total mixed configurable inputs
Digital Outputs 9 programmable relay outputs + shutdown relays
Analog Inputs Up to 30 total mixed configurable inputs
Analog Outputs 3 × 4–20 mA speed readout outputs
CAN Communication Ports N/A
RS485 / Serial Ports 3 Modbus ports (RS-232 / RS-422 / RS-485)
Ethernet Ports N/A
Mounting Type Bulkhead Mount / Panel Mount
Nominal Frequency 47–63 Hz
Degree of Protection IP56 (when installed in enclosure)